EasyManua.ls Logo

Wilo Control MS-L Series - Functions

Wilo Control MS-L Series
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation en
Installation and operating instructions Wilo-Control MS-L 25
3
Control MS-L2...
SSM Alarm
161514131211
Fig.15: Terminal strip sensors: external alarm
signal for high water
An external alarm signal (horn, flashing light, etc.) can be connected for the high water
alarm:
ƒ Contact type: potential-free changeover contact
ƒ Contact load:
Minimum: 12VDC, 10mA
Maximum: 250VAC, 1A
Insert the connection cables laid by the customer through the threaded cable glands
and secure. Connect the wires to the terminal strip according to the connection dia-
gram.
Switchgear Normally open contact
(NO)
Normally closed contact
(NC)
Control MS-L1...
Control MS-L2...
Terminal 15/16 Terminal 14/15
6.6 Functions
The switchgear is equipped with the following functions. All functions are switched off
at the factory. The functions must be switched on as required.
Inputs/outputs
Control MS-L 1...
Control MS-L 1...-O
Control MS-L 1...-LS
Control MS-L 2...
Control MS-L 2...-O
Control MS-L 2...-LS
Internal buzzer
Pump kick
Service interval indicator
Monitoring operating parameters
Follow-up time
Adjustable switching points for pump ON and high water*
Key
• = available, − = not available
* The switching points can be selected from eight sets of parameters for the respective
lifting unit.
6.6.1 Internal buzzer
ON DIP
1 2 3 4 5 6 7
8
Fig.16: DIP switch1: internal buzzer
The internal buzzer can also issue audible warning messages in addition to the visual in-
dicator. Switch the internal buzzer on/off via DIP7 on DIP switch1:
ƒ “ON” position: Buzzer on
ƒ “OFF” position: Buzzer off
6.6.2 Pump kick
ON DIP
1 2 3 4 5 6 7
8
Fig.17: DIP switch1: Pump kick
To prevent prolonged standstill periods for the connected pumps, a periodic test run
can be performed (pump kick function). A 2s test run takes place after a standstill
period of 24h for the respective pump.
Switch the pump kick on/off via DIP6 on DIP switch1:
ƒ “ON” position: Pump kick on
ƒ “OFF” position: Pump kick off
6.6.3 Service interval indicator
A service interval indicator can be switched on to increase operational reliability. The
time is recorded continuously when the mains voltage is switched on. After the interval
has elapsed, a visual signal is emitted by means of the yellow LED on the front. NO-
TICE!There is no audible signal and the collective fault signal is not activated!

Table of Contents

Related product manuals