DSE 3110 CONTROL
FAULT CODES
ICON
DESCRIPTION
AUXILIARY INPUTS
Auxiliary inputs can be user congured and will display the message as
written by the user.
FAIL TO START
The engine has not red after the preset number of start attempts
FAIL TO STOP
The module has detected a condition that indicates that the engine is running
when it has been instructed to stop.
NOTE:- ‘Fail to Stop’ could indicate a faulty oil pressure sensor
-Ifengineisatrestcheckoilsensorwiringandconguration.
LOW OIL PRESSURE
The module detects that the engine oil pressure has fallen below the low oil
pressure pre-alarm setting level after the Safety On timer has expired.
ENGINE HIGH OIL
TEMPERATURE
The module detects that the engine oil temperature has exceeded the high
engine temperature pre-alarm setting level after the Safety On timer has
expired.
UNDERSPEED
The engine speed has fallen below the underspeed pre alarm setting
OVERSPEED
The engine speed has risen above the overspeed pre alarm setting
BATTERY UNDER
VOLTAGE / BATTERY
OVER VOLTAGE
The DC supply has fallen below or risen above the low/high volts setting
level.
GENERATOR UNDER
VOLTAGE
The generator output voltage has fallen below the pre-set pre-alarm setting
after the Safety On timer has expired.
GENERATOR OVER
VOLTAGE
The generator output voltage has risen above the pre-set pre-alarm setting.
GENERATOR UNDER
FREQUENCY
The generator output frequency has fallen below the pre-set pre-alarm
setting after the Safety On timer has expired.
GENERATOR OVER
FREQUENCY
The generator output frequency has risen above the pre-set pre-alarm
setting.
INTERNAL MEMORY
ERROR
Either the conguration le or engine le memory is corrupted. Contact your
supplier for assistance.