TROUBLESHOOTING TABLES
ENGINE WILL NOT CRANK
1. Low/dead battery.
2. Blown DC fuses 2 amp or 25 amp.
3. Defective DSE3110.
4. Defective key switch.
4. Loose or dirty battery terminals.
5. Defective starter.
6. Defective start solenoid.
7. Locked up engine genset.
8. Defective engine harness.
9 Improper battery voltage to start solenoid, fuel
pump or fuel solenoid.
ENGINE CRANKS BUT WILL NOT START
1. Improper fuel delivery to the unit.
2. Fuel supply shut off.
3. Fuel tank empty.
4. Air in the fuel system.
5. Engine fuel solenoid has not opened.
6. Defective fuel pump.
7. Defective fuel solenoid
8. Defective engine harness.
9 Improper battery voltage to fuel pump or fuel
solenoid.
ENGINE STARTS AND THEN STOPS AND ALARM LIGHT
COMES ON
1. Engine oil pressure is low.
2. Engine has high water temperature.
3. Refer to fault code on DSE3110
ENGINE WILL NOT COME UP TO SPEED AFTER IT
STARTS
1. Insufcient fuel volume getting to the unit.
a. Too small of fuel line.
b. Fuel racks not opened properly.
2. Governor is defective.
3. AC short in generator components.
NO AC OUTPUT FROM GENERATOR
1. Defective diode.
2. Defective voltage regulator.
3. Defective rotor.
4. Defective stator.
5. Defective exciter rotor.
6. Defective exciter stator.
7. AC short in the output leads.
8. Defective/open generator output breaker.