Appendix: Technical data
It may be necessary to also observe additional country-specific regulations.
The local power supply must be constructed according to the currently valid
IEC364 (DIN VDE 0100). An isolated ground outlet or acountry-specific
single-phase outlet for single-phase connection, or a5-pole CEE/CEKON socket
per EN 60309or acountry-specific multi-pole socket for athree-phase connection,
must be available near the machine. The sockets are part of the customer‘s on-site
installation. The mains cable must not come into contact with hot surfaces. If the
mains cable for this device is damaged then it must be replaced by our service
personnel or asimilarly qualified person, in order to prevent hazards.
In order to avoid possible faults from arising on our shielded data lines due to
potential equalization currents between the devices, an additional potential
equalization unit should be planned for devices connected to the vending system.
(See EN 60309)