10
Parameter mode
e.g. gradient
Display mode
e.g. actual flow
temperature
Contractor level
Pressing key changes the display to contractor
level.
The contractor level is segregated into display
and parameter mode.
Individual displays (e.g. A:01) and parameters
(e.g. P:01) are shown in sequence after
pressing .
In parameter mode you can change the values
displayed above the r.h. rotary selector.
Display list:
Index Explanation Unit
A 01 Set flow temperature °C
A 02 Actual flow temperature °C
A 03 Actual DHW temperature °C
Parameter list
Index Explanation Setting range Factory setting
P 03 Set DHW temperature 15 - 65 °C for boilers type E 60 °C
40 - 63 °C for boilers type K 60 °C
P 04 Pasteurisation 00 - 01 00
GB 01 Flow temperature hysteresis 1 - 20
GB 04 Upper fan speed - central heating 30 - 100
GB 05 Frost protection outside temperature -10 - 10
GB 06 Heating circuit pump mode 0 - 1
GB 07 Heating circuit pump run-on 1 - 30
GB 08 Maximum set flow temperature 40 - 90
GB 09 Cycle block 0 - 30
GB 13 Input 1 0 - 5
GB 14 Output 1 0 - 9
GB 15 DHW cylinder hysteresis 1 - 15
List of displays and parameters
Note: Parameters GB01 to GB15 are not avaliable for all boilers; for descriptions see the
installation instructions of the relevant boiler.
Contractor level
Parameters GB 01 - 15 must only be modified by a heating contractor. Incorrect operation
can lead to system faults.
Parameter 5 (outside temperature frost protection) is only effective with an outside
temperature sensor.
Warning
See installation
instructions for
gas fired boiler