3061916_0611 15
Subject to the solar module used, different parameters are available.
Parameters used with SM1 solar module:
Parameter
BM
Parameter
BM-Solar
Explanation
Setting range Factory
setting
min. max.
SOL 01 P 01
Startdifferentialsolarcylinder 5K 30K 8K
SOL 02 p 02
Stopdifferentialsolarcylinder 2K 20K 4K
SOL 03 P 03
Collectorcoolingfunction 0(OFF) 1(ON) 0
SOL 04 P 04
Criticalcollectortemperature 90°C 150°C 110°C
SOL 05 P 05
Maximumcollectortemperature 100°C 150°C 130°C
SOL 06 P 06
Maximumcylindertemperature,
solarcylinder
15°C 90°C 60°C
SOL 07 P 07
Assignment,solarcylinder 0 8 0
SOL 08 P 08
Capturingtheamountofheat 0(OFF) 4 0
SOL 09 P 09
P 08=0→P 09 Notadjustable
P 08=1→
Pulsevalue,pulsegenerator
P 08=2→
Constantflowrate
P 08=3or4→
Pulsevalue
externalheatmeter
0l/pulse
0l/min
-2
99.5l/pulse
99.5l/min
1
1l/pulse
1l/min
0
SOL 10 P 10
Glycolselection:
0=Water
1=TyfocorL(Anro)
2=TyfocorLS(AnroLS)
3=Propyleneglycol
4=Ethyleneglycol
0 4 1
SOL 11 p 11
BUSfeed 0 2 2
SOL 27 * p 27 *
Tubecollectorfunction 0(OFF) 2 0
SOL 28 * p 28 *
Frostprotectionfunction 0(OFF) 1(ON) 0
SOL 33 * P 33 *
Hysteresis,solarcylinder 0.5K 5K 1K
SOL 36 * P 36 *
Solarcylinderemergency
shutdown
60°C 95°C 95°C
SOL 39 * P 39 *
Minimumcollectorlimit -25°C 90°C 10°C
SOL 41 * P 41 *
Functioncheck,owrate 0(OFF) 1(ON) 0
SOL 42 * P 42 *
Functioncheck,gravitybrake 0(OFF) 60°C 40°C
SOL 44 * P 44 *
Reversecoolingfunction 0(OFF) 1(ON) 0
SOL 51 * P 51 *
Proportionofglycolinwater
P 10=0→P 51 Notadjustable
P 10 =1:TyfocorL(Anro)
P 10 =2→P 51 Notadjustable
P 10 =3→P 51 Notadjustable
P 10 =4→Ethyleneglycol
----
20 %
----
----
20 %
----
75%
----
----
80 %
----
45%
----
----
45%
SOL 6O p 60
Relaytest 1 5 1
Parameter level
For function descriptions of the individual parameters, see the SM solar module instruction
manual.
*ParametersonlyeffectivefromsoftwareversionSM1/SM2228_04.