12.Maintenanceinstructions
Check and clean at regular intervals.
Cleaning the heat exchanger (possible without replacing the PHE):
- Vacuum, taking care not to bend the ns
- Clean with water (non-pressurised) or a soapy solution
Removal of the plate elements is possible using an appropriate retaining rail set.
- Cleaning methods that use high pressure (e.g. steam jet / high pressure
washer) carry a risk of irreparable mechanical damage to the plate heat
exchanger.
- Before restarting, replace the factory-tted seal on the condensate pan if
this was removed during maintenance on the plate heat exchanger.
Please
note
Countercurrentplateheat
exchanger(PHE)
Electricalequipment - Regularly check the electrical equipment of the unit.
- Replace loose connections and faulty cables immediately.
- Regularly check the earth conductor.
Servomotorsonthedampers The motors are maintenance-free.
At regular intervals, check that the connection from the servomotor to the
damper drive is rmly seated.
Trap Regularly check the DN 50 trap (accessories) for possible soiling and clean if
required. (See checklist).
Rell the trap with water before returning into use.