Heat Recovery unit CWL-300(B) / CWL-400(B) with option PCB 13
Faults Chapter 5
Fault code Cause Action user Action installer
F2
The input fan has stopped. Contact the installer. Replace the input fan.
F5
The output fan has stopped. Contact the installer.
Replace the output fan
.
F9
The temperature sensor that
measures the temperature of
WKHLQSXWDLULVGHIHFWLYH
The appliance operates as ex-
pected, but the bypass is out of
operation.
Contact the installer.
Check the wiring from the sensor to the
basic pcb.
Check the sensor connection to the
wiring.
Replace the sensor.
F10
The temperature sensor that
measures the temperature of
WKHRXWSXWDLULVGHIHFWLYH
The appliance operates as ex-
pected, but the bypass is out of
operation
.
Contact the installer.
Check the wiring from the sensor
to the basic pcb.
Check the sensor connection to
the wiring.
Replace the sensor
.
F11
The postheater sensor is not
FRQQHFWHGGHIHFWLYHVKRUWFLU-
cuited or it has come loose.
CWL operates as expected, but
the postheater is out of opera-
tion.
Contact the installer.
Check the wiring and the connection to
the postheater sensor.
Replace the sensor.
5.1 Fault codes table CWL 300/400(B) with option pcb