What to do if starter no response on Woodward easYgen-1800?
- Mmatthew15Sep 6, 2025
If the Woodward Control Unit starter does not respond, check the starter connections and the starting batteries.
What to do if starter no response on Woodward easYgen-1800?
If the Woodward Control Unit starter does not respond, check the starter connections and the starting batteries.
How to resolve controller emergency stop on Woodward easYgen-1800?
If the Woodward Control Unit experiences an emergency stop, check if the emergency stop button works properly, verify whether the starting battery's positive pole is connected to the emergency stop input, and check whether the circuit is open.
How to fix RS485 communication if it's abnormal on Woodward easYgen-1800 Control Unit?
If the Woodward Control Unit's RS485 communication is abnormal, check the connections, ensure the COM port setting is correct, verify that the RS-485 connections of A and B are not reverse connected, check if the RS485 transfer model is damaged, and check if the communication port of the computer is damaged.
What to do if Woodward Control Systems genset shutdown?
If the Woodward Control Systems genset experiences a shutdown, examine the following: ensure the water/cylinder temperature is within limits, verify the genset AC voltage, and check the DC fuse.
What to do if Woodward Control Systems low oil pressure alarm after crank disconnect?
If the Woodward Control Systems triggers a low oil pressure alarm after crank disconnect, check the oil pressure sensor and its connections.
What to do if Woodward Control Systems high water temp. alarm after crank disconnect?
If the Woodward Control Systems triggers a high water temperature alarm after crank disconnect, check the temperature sensor and its connections.
What to do if Woodward Control Systems ECU warning or shutdown?
If the Woodward Control Systems ECU displays a warning or initiates a shutdown, get information from the LCD of the alarm page. If there is a detailed alarm, check the respective engine. If there is no detailed alarm, please refer to the relevant section of the engine manual as specified in the SPN alarm code.
What to do if Woodward Control Systems RS485 communication is abnormal?
If the Woodward Control Systems RS485 communication is abnormal, check the connections, verify if the COM port setting is correct, check if the RS-485 connections of A and B are reverse connected, check if the RS485 transfer model is damaged, and see if the communication port of the computer is damaged.
Why Woodward Control Systems genset running while ATS not transfer?
If the Woodward Control Systems genset is running but the ATS is not transferring, check the ATS and inspect the connections between ATS and controllers.
What to do if Woodward Control Systems shutdown alarm in running?
If the Woodward Control Systems shows a shutdown alarm while running, check the switch and its connections according to the information on LCD, and inspect auxiliary input ports.
Power Supply Voltage | 24 VDC |
---|---|
AC System | 1-phase, 2-wire |
Operating Temperature | +70 °C |
Operating Temperature Range | -40°C to +70°C |
Communication Ports | RS-485 |
Communication | Modbus RTU |
Protection Class | IP20 |
Supported Protocols | Modbus RTU |
Manual overview, revision history, and notes.
Includes general information, copyright, and disclaimer details.
Information on service, warranty terms, and potential voidance.
Covers general safety guidelines and intended application of the device.
Defines the proper and intended application of the easYgen unit.
Lists the various status screens available on the Human Machine Interface (HMI).
Details status information accessible via the ToolKit-SC software.
Describes the buttons, indicators, and display on the controller's front panel.
Explains how warnings and alarms are visualized using LEDs and horns.
Outlines the three main operation modes: AUTO, MANUAL, and STOP.
Covers the procedures for starting and stopping the genset.
Lists and explains all alarms and warnings generated by the controller.
Lists alarms that cause the generator to shut down.
Lists alarms that cause a trip and stop condition for the generator.
Lists alarms that cause a trip condition without stopping the generator.