EasyManua.ls Logo

Worcester danesmoor 26/32

Worcester danesmoor 26/32
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
* NOTE: For use on conventional flue only.
** NOTE: The flue gas temperature is measured in the gas sampling hole on the flue outlet plate. The probe should be inserted to a depth of 50mm and angled towards the flue outlet.
The temperature measured is not an absolute flue gas temperature and is for general guidance purposes only!
NOTE: The pump pressure given is for general guidance only as variations in nozzle output can be up to ± 15%. It is, therefore, essential that the air is adjusted to give the correct CO
2
value.
NOTE: The nozzle type used on 28 Sec. Kerosene outputs are nozzles calibrated specifically for use with 28 Sec. Kerosene which gives less variation in nozzle output than the standard
35 Sec. Gas Oil nozzles. However, if a 28 Sec. Kerosene nozzle is not available at servicing or commissioning it is appropriate to install a 35 Sec. Gas Oil nozzle providing the output, spray
angle and pattern of the nozzle is the same as the 28 Sec. Kerosene nozzle (e.g. 0.75 80°EH may be replaced with a 0.75 80°H).
~NOTE: At 70kW the air guide should be removed (See Fig. 24)
28 Sec. Kerosene 0.85 80°EH 110 2.36 2.99 225 11.0-11.5 10 28.5 97,000 26 89,000
28 Sec. Kerosene 0.85 80°EH 130 2.66 3.37 240 11.0-11.5 15 32 109,000 29 99,000
28 Sec. Kerosene 1.00 80°EH 130 2.95 3.74 245 11.5-12.0 20 35.5 121,000 32 109,000
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
26/32 Table 7. Electro Oil Sterling 40 Burner (See Fig. 23) RS Balanced Flue Appliance
Fuel Nozzle
Pump
Pressure
(p.s.i.)
Fuel Flow
Rate
Flue Gas
Temp.
(°C)**
%CO
2
Approx.
Air
Setting
Appliance
Input
kW Btu/hr kW Btu/hr
Output
Kg/h l/h
28 Sec. Kerosene* 1.00 60°ES 130 2.90 3.67 185 11.5-12.0 7.50 35 119,000 32 109,000
28 Sec. Kerosene* 1.25 60°S 130 3.78 4.78 200 12.0-12.5 14.25 45 155,000 41 140,000
28 Sec. Kerosene* 1.65 60°S 115 4.64 5.87 230 12.0-12.5 23.50 56 191,000 50 171,000
35 Sec. Gas Oil* 0.65 80°S 185 2.95 3.47 190 11.0-11.5 8.75 35 119,000 32 109,000
35 Sec. Gas Oil* 0.85 60°S 200 3.83 4.51 205 11.0-11.5 17.00 45 155,000 41 140,000
35 Sec. Gas Oil* 1.10 60°S 185 4.71 5.54 235 12.0-12.5 25.00 56 191,000 50 171,000
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
32/50 Table 8. Electro Oil Sterling 50 Burner (See Fig. 23) Conventional Flue Appliance (CF)
Fuel Nozzle
Pump
Pressure
(p.s.i.)
Fuel Flow
Rate
Flue Gas
Temp.
(°C)**
%CO
2
Approx.
Air
Setting
Appliance
Input
kW Btu/hr kW Btu/hr
Output
Kg/h l/h
28 Sec. Kerosene* 1.35 60°S 165 4.62 5.85 205 11.5-12.0 3 55.5 190,000 50 171,000
28 Sec. Kerosene* 1.75 60°S 155 5.55 7.03 225 12.0-12.5 4 67 229,000 60 205,000
~28 Sec. Kerosene* 2.00 60°S 145 6.47 8.19 235 12.0-12.5 4.5 78 268,000 70 239,000
35 Sec. Gas Oil* 1.00 60°S 240 4.69 5.52 205 11.0-11.5 3 55.5 190,000 50 171,000
35 Sec. Gas Oil* 1.35 60°S 180 5.63 6.62 225 12.0-12.5 4 67 229,000 60 205,000
~35 Sec. Gas Oil* 1.75 60°S 160 6.57 7.73 235 12.0-12.5 4.5 78 268,000 70 239,000
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
50/70 Table 9. Electro Oil Inter B20B Burner (See Fig. 24) Conventional Flue Appliance (CF)
Fuel Nozzle
Pump
Pressure
(p.s.i.)
Fuel Flow
Rate
Flue Gas
Temp.
(°C)**
%CO
2
Approx.
Air
Setting
Appliance
Input
kW Btu/hr kW Btu/hr
Output
Kg/h l/h

Related product manuals