DISPLAY INFORMATION
6 720 648 726 (2011/07)
79
e [a/1/1| e [8/2/3| e Fault:
RC35-HK1 remote control. No remote
control assigned, although frost protection
type "FROST" has been set.
No Off Since there is no
actual room
temperature
information, room
influence and
optimization of the
switch times do not
work. The EMS
works on the basis
of the values last set
on the remote
control.
e [a/1/1| e [8/2/4| e Fault:
RC35-HK2 remote control. No remote
control assigned, although frost protection
type "FROST" has been set.
e [a/1/1| e [8/2/6| e Fault:
RC35-HK1 temperature sensor. The external
temperature sensor of the remote control
(control unit) of heating circuit 1 is
defective.
No Off Since there is no
actual room
temperature
information, room
influence and
optimization of the
switch times do not
work. The EMS
works on the basis
of the values last set
on the remote
control.
e [a/1/1| e [8/2/7| e Fault:
RC35-HK2 temperature sensor. The external
temperature sensor of the remote control
(control unit) of the heating circuit is
defective.
e [a/1/2| e [8/1/5| e Fault:
The contacts to the switch sensor have
shorted or are interrupted, the sensor has
been connected incorrectly or is defective.
No Off Limited operation of
all heating programs,
holiday function,
fault list.
e [a/1/2| e [8/1/6| e Fault:
WM10 not available or no communication.
WM10 or bus circuit connected incorrectly
or defective, WM10 is not recognized by the
RC35.
No Off Heating circuit pump
1 is activated
continuously.
Display codes
Display code LED on
UBA 3
Other effects
z
Main
display
code
z
Sub
display
code
z
Key to display code
Reset
requi-
red?
Table 24 Display codes