34
3-10Matsushita FP series PLC
OP can communicate with Matsushita FP series PLC through programming port or expansion
port.
3-10-1Connection unit
Series
CPU Connected
module
Port Cable Choose PLC type in
OP20
FP
FP0 CPU
RS232
Diagram 1
Matsushita FP0/FP1
series
FPM
CPU
RS232
Diagram 1
FPX
CPU
RS232
Diagram 1
FP
CPU
RS232
Diagram 1
FP2
CPU
RS232
Diagram 1
CPU RS232
RS232
Diagram
2
FP2SH
CPU
RS232
Diagram 1
CPU RS232
RS232
Diagram 2
FP1
CPU RS232
RS232
Diagram 2
CPU RS232
RS422
Diagram 3
FP3 CPU RS232
RS422
Diagram 4
FP10SH
FP10S
CPU RS232
RS232
Diagram 2
FP-e CPU
RS232
Diagram 1
Note: Only FP0-CXXCXX has RS232 port.
3-10-2Communication parameters
OP software settings
Parameters
Recommend
settings
Choices of settings Note
PLC type
Matsushita
( FP1/FP0 )
Choose the correct PLC type in OP20
Port
RS232
Data bit
8
7/8
Accord with PLC port parameters
Stop bit
1
1/2
Accord with PLC port parameters
Parity Odd parity Even /odd /no parity Accord with PLC port parameters
Baud rate 9600 4800/38400/9600/
115200/19200/187500
Accord with PLC port parameters
Station no. 1 0~255
The default parameters of Matsushita FP series PLC: 9600, 8, 1, odd parity, station no.1