VESDA-EVES-A10-P Product Guide
74 www.xtralis.com
Parameter Default Values Range Affected by Return to
Factory Defaults
command
Minimum Maximum
Ethernet /WiFi
connection idle
timeout (hours)
No timeout 15 minutes 24 hours No
Smoke Thresholds (See recommendation for lowest Alert in Section 6.)
Alarm Level - Day and
Night - Sector 1 to 4
Alert 0.08 % obs/m
(0.025 % obs/ft)
0.005 % obs/m
(0.0016 % obs/ft)
2.0 % obs/m
(0.625 % obs/ft)
Yes
Action 0.14 % obs/m
(0.044 % obs/ft)
0.005 % obs/m
(0.0016 % obs/ft)
2.0 % obs/m
(0.625 % obs/ft)
Yes
Fire 1 0.20 % obs/m
(0.0063 % obs/ft)
0.010 % obs/m
(0.0031 % obs/ft)
2.0 % obs/m
(0.625 % obs/ft)
Yes
Fire 2 2.0 % obs/m
(0.625 % obs/ft)
0.02 % obs/m
(0.0063 % obs/ft)
20.0 % obs/m
(6.25 % obs/ft)
Yes
Significant Smoke
Change – Logging
0.005 % obs/m
(0.0016 % obs/ft)
0.0001 % obs/m
(0.000031 % obs/ft)
0.2 % obs/m
(0.0063 % ofs/ft)
Yes
Significant Smoke
Change - VESDAnet
0.005 % obs/m
(0.0016 % obs/ft)
0.0001 % obs/m
(0.000031 % obs/ft)
0.2 % obs/m
(0.0063 % ofs/ft)
Yes
Scanning – Sector
Scan Time
8 seconds 8 seconds 15 seconds Yes
Scanning – Scan
Delay
3 0 10 Yes
Work Days Monday through
Friday
n/a n/a Yes
Day Night Changeover Time
l Enabled Unchecked Unchecked Checked Yes
l Day Start 7 AM n/a n/a Yes
l Night Start 7 PM n/a n/a Yes
Holidays
l Enabled Unchecked Unchecked Checked Yes
l Start Holiday
Date
Blank n/a n/a Yes
l End Holiday Date Blank n/a n/a Yes
Air Flow
Air flow thresholds
l Major High 130% 105% 200% Yes
l Minor High 120% 105% 200% Yes
l Minor Low 80% 25% 95% Yes
l Major Low 70% 25% 95% Yes
Delay 30 seconds 15 seconds 250 seconds Yes
Significant Flow
Change
2.0 L/min 0.5 L/min 5 L/min Yes
Table5-4: Default Settings (continued...)