VESDA by Xtralis VESDAVLSProduct Guide
www.xtralis.com 15
Parameter Default Values Range Access Level
Minimum Maximum
Scan Threshold Delay 3 seconds 0 seconds 10 seconds Adm
Smoke Change...
Change By
0.02% obs/m
(0.0063% obs/ft.)
0.005% obs/m
(0.0016% obs/ft.)
1.990% obs/m
(0.6218% obs/ft.)
Adm
Smoke Change...
Minimum Interval
2 seconds 2 seconds 10 seconds Adm
UL Version On Selectable Selectable Adm
Units SI Selectable Selectable Adm
Weekend Saturday and
Sunday
Selectable Selectable Adm
Table 3-2: Default settings and permissible thresholds (continued...)