VSC Software Configuration
6-22 VESDA Student Workbook
General Purpose Inputs tab
• General Purpose Inputs –
remote input device for the
detector that can be
programmed to perform one of
several functions
• Button Lockout – the Reset and
Disable buttons on the front of
the detector are unable to be
used (if selected)
Relays tab
• Configure according to the
illustration
• Click Apply
• Relays rated at 2a 30VDC
Note: Trouble Relays normally
energized making them Failsafe.
When commissioning test Relays
for operation using an Ω meter.