Please complete checklist item 7:
7. Configure a Detector
a. Double-click the detector
On the General tab:
Verify the Network Name and Location
On the Ethernet tab:
Verify IP Address, Subnet Mask, and Default Gateway
On the Smoke Thresholds tab:
Set Delay (sec):
Fire 2 10
Fire 1 5
Action 3
Alert 1
Activity
Please complete checklist item 7:
7. Configure a Detector
On the Air Flow tab:
Deselect Pipes in Use 2, 3,
and 4
Set Delay (sec) to 15
On the Relays tab:
Configure according to the
illustration
Click Apply
Click OK