2) Pre-Commissioning (at site)
Power up system
Takes approximately 15 seconds to power up
Different models start up differently (read commissioning guide or product manual)
Preliminary system check
Verify VSC communication
Normalize airflow
Pipe Integrity Smoke Test
2) Pre-Commissioning (at site)
Pipe Integrity Smoke Testing
Test pipe integrity in any typical customer site
Suitable for the testing of standard sensitivity fire detection systems
Items needed:
Smoke source
Stopwatch
Fire extinguisher (dependent on smoke source)
Shows an increase of smoke on detectors with a display module fitted or monitored by VSC