6
16. Create a Two Grilles Pipe Network ❑
a. Copy detector
1. Click Ceiling detector
• Click Edit
• Select Copy
• Click Aspire Project
• Click Edit
• Select Paste
• Right-click and select Rename
• Rename Copy of Ceiling to Two Grilles
2. Click the + to expand the detector
• Select Ceiling Right
• Right-click
• Select Delete
• Click OK
• Select Ceiling Left
• Right-click
• Select Delete
• Click OK
b. Configure for two grille coverage
1. Select Two Grilles detector
• Set Detector Type to VEP-1P
2. Click the Add a new pipe to this detector icon
• Name the pipe Two Grilles Pipe
• Click the Simple branch icon
• Set the Number of bends before 1
st
branch to 0
• Click Finish
3. Click Calculate
4. Click the + to expand the Two Grilles Pipe
• Select Section 1
• Click Endcap
• Set the Hole Diameter to 0
• Click the first row in the Item column (Bend 90)
• Click the red X (in the toolbar)
• In the Relative Distance column, type 14, 2, 1, 1, 1, 2
• Press Enter
• Click Calculate
5. With Section 1 still selected:
• Click Edit
• Select Copy
6. Click Section 2
• Click Edit
• Select Paste
• Click Calculate