15. Project Configuration ❑
a. Double-click the ASPIRE33 desktop icon
b. Verify Enforced Limit is set to NFPA
c. Verify Interface is set to Advanced
d. Rename New Project
• Right-click New Project
• Select Rename
• Change the name to Aspire Project
• Click Enter
e. Add a detector
• Click Add a new detector to the project icon
• Set Detector Type to: VEP Detector
• Change Detector Name to Ceiling
• Set Aspirator Speed to 2
f. Add pipe
1. Click Add a new pipe to this detector icon
• Name the pipe Ceiling Right
• Select Simple pipe
• Set Number of bends before 1
st
Hole to 1
• Click Finish
2. In the Toolbar, click the Calculate icon
3. In the Direction column:
• Double-click the F elbow
• Select R to redirect the pipe
g. Copy pipe
1. From the Device Tree, click Ceiling Right pipe
• Click Edit
• Select Copy
• Click Edit
• Select Paste
• Rename Copy of Ceiling Right to Ceiling Left
2. In the Direction column:
• Double-click the R elbow
• Select L to redirect the pipe
3. In the Toolbar, click the Calculate icon
4. In the lower left-hand corner, click the Enlarge View arrow
• Click Save Design icon