EasyManua.ls Logo

Xtralis VESDA VLS - Page 264

Xtralis VESDA VLS
367 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VESDA PipeNetwork Design Guide VESDA by Xtralis
20 www.xtralis.com
The details of the number and size of the holes to be used can be found in Table 4-1.
Legend
A Holes with same orientation
B Rubber Grommet
C Air flow
Figure 4-20: Small duct sampling - top view
For small ducts, holes are nominally spaced each 200 mm (8 in)
Table 4-1: Hole size for a small duct
Duct width No. of holes Hole Ø Nominal pipe flow
rate (L/min.) (cfm)
300 mm (12 in) 2 6 mm 15/64 in 39.0 L/min. (1.4 cfm)
500 mm (20 in) 3 5 mm 13/64 in 40.7 L/min. (1.4 cfm)
700 mm (28 in) 4 4 mm 5/32 in 35.6 L/min. (1.26 cfm)
900 mm (36 in) 5 4 mm 5/32 in 42.8 L/min. (1.51 cfm)
Large Ducts: Width 1 - 2 m (3 - 7 ft)
For large ducts, the inlet pipe is recommended to have two branches. Figure 4-22 shows a side view of a duct
section with the relative insertion positions for the inlet and exhaust pipes. Both inlet branches enter at a
quarter of the height of the duct from the top and bottom where H is the height of the duct.
The exhaust pipe should be inserted approximately 0.5 m (1.64 ft) further downstream in the middle of the
height of the duct.
Legend
A Duct Flow
B Exhaust pipe H/2
C Inlet pipe H/4
D 500 mm (20 in.)
Figure 4-21: Large duct sampling - side view
The diagram below shows a cross-section view of a duct with the locations of the inlet branches and exhaust
pipe. A recommendation of hole size and spacing arrangement is shown in Table 4-2.

Table of Contents

Other manuals for Xtralis VESDA VLS

Related product manuals