EasyManuals Logo

Xylem HYDROVAR HV 2.022 User Manual

Xylem HYDROVAR HV 2.022
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #95 background imageLoading...
Page #95 background image
95
Error probable cause measure
OVERLOAD
ERROR 12
Power limit of the HYDROVAR
is exceeded
check Parameter RAMP 1/2
[0215/0220] (too short) and BOOST
[0265] (too low)
check motor connection
(star/delta) and cable
Pump blocked
Motor turns in the wrong direction
before running
(Non return-valve defect)
Not allowed operation point or
MAX. FREQUENCY [0245] too high
check also the BOOST [0265].
OVERVOLTAGE
ERROR 13
DC voltage of the HYDROVAR
too high
Parameter RAMP 2 [0220] too fast
Power supply too high
Voltage peaks too high
(Solution: Line filters, Line
inductance, RC-element)
INVERT. OVERHEAT
ERROR 14
too high temperature inside
the HYDROVAR
no proper cooling
contamination of the motor vents
ambient temperature too high
THERMO MOT/EXT
ERROR 15
An external protective device
connected to terminal X1/PTC
has released (e.g. PTC which is
connected has reached its
release temperature)
close X1/PTC if there is no external
protective device connected
close external on/off switch if
connected to these terminals
For detailed information how the
terminal X1/PTC could be used see
chapter 9.4.3
PHASELOSS
ERROR 16
One phase of the power supply
has been lost -> automatic
power reduction (just available
for the units HV4.055-4.220)
check power supply under full load
– check if phase failure at the input
check circuit breakers
visual inspection of points at the
input terminals
UNDERVOLTAGE
DC voltage of the HYDROVAR
too low
supply voltage too low
phase failure at the input
asymmetry of the phases
COMM LOST
The communication between
the Power Unit and the control
card doesn’t work correctly
check if the addressing of BASIC
Inverter [DIP SW.] has been done
correctly (retry!)
check if each unit has allocated its
own pump address
check if the connection from
control card to the power unit is
made properly (ribbon cable)

Table of Contents