11.2 MASTER / SINGLE Inverter
Each error is shown on the display in plain text and saved in the error memory.
The errors can be reset automatically (depending on the setting in parameter ERROR-RESET
[0615]) or manually in following ways:
cutting the power supply for > 60 seconds
pressing and simultaneously for about 5 seconds
open and close the External ON/OFF (Terminals X3/7-8)
No error-message on the display
Error probable cause measure
no AUTOSTART after
power failure
Parameter AUTOSTART [08] is
set to OFF
Check parameter AUTOSTART [08]
No operation even system
pressure < set pressure
Pressure higher than the start
value or REGULATION MODE
has been changed to
INVERSE.
check parameter START VALUE [04]
and/or REGULATION MODE [0320]
Error-message on the display
Error probable cause measure
OVERCURRENT
ERROR 11
Current rise at the output too
high
check connection-terminals of the
HYDROVAR
check the connection-terminal of
the motor and the motor-cable
check the windings of the motor
Reset:
cutting of the power supply for >60 seconds.
automatic Error-reset not possible for that kind of failure!

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xylem HYDROVAR HV 2.022 and is the answer not in the manual?

Xylem HYDROVAR HV 2.022 Specifications

General IconGeneral
BrandXylem
ModelHYDROVAR HV 2.022
CategoryController
LanguageEnglish

Related product manuals