EasyManua.ls Logo

YASKAWA GPD 506/P5 - Page 52

YASKAWA GPD 506/P5
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-18 Registers
Drive Parameter Registers continued (Read/Write)
(Continued from previous page)
REGISTER
PARAMETER
PARAMETER
PARAMETER
LIMITS / DESCRIPTION
INITIAL
(in hex)
FUNCTION SETTING VALUE
137h n055 Momentary Power Loss 0 Not Provided
Ridethrough
Method Selection
1 Continuous Operation (power recovery
within 2 seconds) 0
2 Continuous Operation (after power
recovery within control logic time)
138h n056 Speed Search Operation Level 0 to 200% 150%
139h n057 Minimum Base Block Time 0.5 to 5.0 seconds (1)
13Ah n058 V/f Reduction Level during Speed
Search
0 to 100% (1)
13Bh n059 Momentary Power Loss Ridethrough
Time
0.0 to 2.0 seconds (1)
13Ch n060 No. of Auto. Restart Attempts 0 to 10 0
Notes:
1. Initial Value depends on GPD 506 capacity.

Related product manuals