7-19 Registers
Drive Parameter Registers continued (Read/Write)
REGISTER
PARAMETER
PARAMETER
PARAMETER
LIMITS / DESCRIPTION
INITIAL
(in hex)
FUNCTION SETTING VALUE
13Dh n061 Fault Contact Selection 0 Closed during auto. restart 0
at Auto Restart 1 Open during auto. restart
13Eh n062 Prohibit Frequency 1 0.0 to 400.0 Hz 0
13Fh n063 Prohibit Frequency 2 0.0 to 400.0 Hz 0
140h n064 Prohibit Frequency Deadband 0.0 to 25.5 Hz 1.0
141h n065 Elapsed Timer Selection 0 Accumulated time during power on 1
1 Accumulated time during running
142h n066 Elapsed Timer 1 0 to 9999 hours 0
143h n067 Elapsed Timer 2 0 to 27 (x 10,000 hours) 0
144h n068 DC Injection Current 0 to 100% (100%=drive rated current) 50
145h n069 DC Injection Time at Stop 0.0 to 10.0 seconds 0.0
146h n070 DC Injection Time at Start 0.0 to 10.0 seconds 0.0
147h n071 Torque Compensation Gain 0.0 to 3.0 1.0
148h n072 Stall Prevention during Decel 0 Disabled 1
1 Enabled
149h n073 Stall Prevention Level during Accel 30 to 200% (@200% disabled during Accel) (1)
14Ah n074 Stall Prevention Level at Set Freq. 30 to 200% (@200% disabled during running) (1)
14Bh n075 Speed Coincide Frequency 0.0 to 400.0 Hz 0.0
14Ch n076 Frequency Agreed Detect. Width 0.0 to 25.5 Hz 2.0
14Dh n077 Overtorque/ Undertorque Detection
(OL3)
0 Detection disabled
1 Overtorque detect only at set
frequency; operation continues
2 Overtorque detect during all frequency
conditions; operation continues 0
3 Overtorque detect only at set
frequency; coast to stop
Notes:
1. Initial value depends on GPD 506 capacity.