EN 12 YASKAWA ELECTRIC
TOEP C710606 27C - AC Drive J1000 - Quick Start Guide
3 Electrical Installation
3 Electrical Installation
The figure below shows the main and control circuit wiring.
Figure 1
Figure 1 Drive Standard Connection Diagram
SA
Motor
Cooling fan
Forward run/stop
Reverse run/stop
External fault
Fault reset
0 to +10 Vdc
(2 mA)
DIP
switch S3
DC link choke
(option)
<1>
Digital inputs
(default setting)
Fault
J1000
Shield ground
terminal
Thermal relay
(option)
Braking resistor
(option)
Main circuit
Control circuit
Thermal relay for
motor cooling fan
Fault relay
1 MCCB
MC
2 MCCB
r1
s1
t1
R/L1
S/L2
T/L3
S1
S2
S3
S4
S5
-
B1+1+2 B2
R/L1
S/L2
T/L3
MC
THRX
TRX
MC
TRX
MC MA
U/T1
V/T2
W/T3
24
V
MA
MB
MC
IV
+
24
V 8
mA
M
M
r1
s1
t1
FU
FV
FW
U
V
W
SC
AM
AC
+
-
AM
+V
A1
AC
2 k
Ground
10 or less (400 V class)
100 or less (200 V class)
Setting power supply
+10.5 max. 20 mA
For single phase 200 V
power supply, use
R/L1 and S/L2.
Analog monitor
output
Digital output
250 Vac, 10 mA to 1 A
30 Vdc, 10 mA to 1 A
(default setting)
Main speed
frequency
reference.
Multi-function
programmable
Multi-step
speed 1
main/aux switch
2 MCCB
THRX
OFF
ON
MC
SA
SA
Three phase
power supply
for 200 V /400 V
Jumper
DIP switch S1
Sink
Source
Terminals +1, +2, , B1, and B2
are for connecting options.
Never connect power supply
lines to these terminals.
_
Monitor
output
Option unit
connector
main circuit terminal
shielded line
twisted-pair shielded line
control terminal
0 to +10 V (20 k )
(0)4 to 20 mA (250 )
<2>
<3>
<4>
<5>
<6>
<7>