EasyManua.ls Logo

YASKAWA J1000 CIMR-JC series - Page 17

YASKAWA J1000 CIMR-JC series
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Electrical Installation
YASKAWA ELECTRIC
TOEP C710606 27C - AC Drive J1000 - Quick Start Guide
EN 17
Control Circuit Terminal Functions
Type No. Terminal Name (Signal) Function (Signal Level), Default Setting
Multi-
Function
Digital
Inputs
S1
to
S5
Multi-function digital input 1 to 5
Photocoupler inputs, 24 Vdc, 8 mA
Note: Drive preset to sinking mode (NPN). When using
source mode, set DIP switch S3 to “SOURCE” and use an
external 24 Vdc (±10%) power supply.
SC Multi-function input common Sequence common
Analog
Input
A1 Analog input
0 to +10 Vdc (20 k) resolution 1/1000
0/4 to 20 mA (250 ) resolution: 1/500
+V Analog input power supply +10.5 V (max allowable current 20 mA)
AC Frequency reference common 0 V
Multi-
Function
Relay
Output
MA N.O. (fault)
Digital relay output
30 Vdc, 10 mA to 1 A
250 Vac, 10 mA to 1 A
MB N.C. output (fault)
MC Digital output common
Monitor
Output
AM Analog monitor output 0 to 10 Vdc (2 mA or less), Resolution: 1/256 (8 bit)
AC Monitor common 0 V