6 Parameter Table
YASKAWA ELECTRIC
TOEP C710606 27C - AC Drive J1000 - Quick Start Guide
EN 25
C6-02
Carrier
Frequency
Selection
1:2.0 kHz
2:5.0 kHz
3:8.0 kHz
4:10.0 kHz
5:12.5 kHz
6:15.0 kHz
7:Swing PWM
F: User defined
Frequency References
d1-01
to
d1-08
Frequency
Reference
1 to 8
Set the multi-speed references 1 to
8.
d1-17 Jog Speed Jog speed
V/f Pattern
E1-01
Input
Voltage
Setting
Input Voltage
E1-04
Max.
Output
Frequency
For a linear V/f characteristics, set
the same values for E1-07 and
E1-09. In this case, the setting for
E1-08 will be disregarded.
Ensure that the four frequencies
are set according to these rules or
an oPE10 fault will occur:
E1-04 E1-06 > E1-07 E1-09
E1-05
Max.
Output
Voltage
E1-06
Base
Frequency
E1-07
Mid.
Output
Frequency
E1-08
Mid.
Output
Vo l t a g e
E1-09
Min.
Output
Frequency
E1-10
Min.
Output
Vo l t a g e
Motor Data
E2-01
Motor
Rated
Current
Motor rated current in Ampere.
E2-02
Motor
Rated Slip
Motor rated slip in hertz (Hz).
Par. Name Description
(E1-04)(E1-06)(E1-07)(E1-09)
(E1-10)
(E1-08)
(E1-05)
Output voltage
Output frequency
E2-03
Motor
No-Load
Current
Magnetizing current in Ampere.
E2-05
Motor
Line-to-Line
Resistance
Sets the phase-to-phase motor
resistance in ohms.
Digital Input Settings
H1-01
to
H1-05
DI
S1 to S5
Function
Selection
Selects the function of terminals
S1 to S5.
A list of the major functions can be found at the table end.
Digital Output Settings
H2-01
DO
MA/MB
Function
Set the function for the relay
output MA-MB-MC.
Major functions are listed at the end of the table.
Analog Input Setting
H3-01
A1 Signal
Level Sel.
0:0 to +10 V (neg. input is zeroed)
1:0 to +10 V (bipolar input)
2:4 to 20 mA (9 bit input)
3:0 to 20 mA
H3-03 A1 Gain
Sets the input value in % at 10 V/
20 mA analog input.
H3-04 A1 Bias
Sets the input value in % at 0 V/0
mA/4 mA analog input.
Analog Input Setting
H4-01
AM
Monitor
Selection
Enter value equal to U1-
monitor values. Example: Enter
“103” for U1-03.
H4-02 AM Gain
Sets terminal AM output voltage
equal to 100% monitor value.
H4-03 AM Bias
Sets terminal AM output voltage
equal to 0% monitor value.
Motor Overheat Protection
L1-01
Motor
Overload
Prot. Sel.
Sets the motor overload
protection.
0:Disabled
1:Standard fan cooled motor
2:Standard blower cooled motor
L1-02
Motor
Overload
Prot. Time
Sets the motor overload protection
time in min. Normally no change
is necessary.
Par. Name Description

Related product manuals