7 Troubleshooting
EN 30
YASKAWA ELECTRIC
TOEP C710606 27C - AC Drive J1000 - Quick Start Guide
oPE03
A contradictory setting is assigned to
multi-function contact inputs H1-01 through to
H1-05.
The same function is assigned to two inputs
(this excludes “External fault” and “Not
used”).
Input functions which require the setting of
other input functions were set alone.
Input functions that are not allowed to be used
simultaneously have been set.
Fix any incorrect settings.
Refer to the instruction manual for more
details.
oPE05
No option unit is installed and one of the
following is true:
b1-01 = 2 or 3
b1-02 = 2
Install the required option unit.
Correct the values set to b1-01 and b1-02.
oPE10
The V/f pattern setting is incorrect.
Check the V/f pattern settings.
Refer to the instruction manual for more
details.