8 Instructions for UL and cUL
YASKAWA ELECTRIC
TOEP C710606 27C - AC Drive J1000 - Quick Start Guide
EN 33
Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors; refer to national state or local
codes for wiring. Use a class 2 (UL listed) power supply for the control circuit terminal.
Table 2 Control Circuit Terminal Power Supply
Drive Short-Circuit Rating
This drive has undergone the UL short-circuit test, which certifies that during a short circuit
in the power supply the current flow will not rise above 31,000 Amps maximum at 240 V for
200 V class drives and 440 V for 400 V class drives.
The MCCB and breaker protection and fuse ratings (refer to the preceding table) shall be
equal to or greater than the short-circuit tolerance of the power supply being used.
Suitable for use on a circuit capable of delivering not more than 31,000 RMS symmetrical
amperes for 240 V in 200 V class drives (up to 440 V for 400 V class drives) motor
overload protection
Drive Motor Overload Protection
Set parameter E2-01 (motor rated current) to the appropriate value to enable motor overload
protection. The internal motor overload protection is UL listed and in accordance with the
NEC and CEC.
2A0012 A6T25 25 FWH-70B 70
2A0020 A6T40 40 FWH-90B 90
Three-Phase 400 V Class
4A0001 A6T3 3 FWH-40B 40
4A0002 A6T6 6 FWH-40B 40
4A0004 A6T15 15 FWH-50B 50
4A0005 A6T20 20 FWH-70B 70
4A0007 A6T25 25 FWH-70B 70
4A0009 A6T25 25 FWH-90B 90
4A0011 A6T30 30 FWH-90B 90
Input / Output Terminal Signal Power Supply Specifications
Multi-function contact output
(digital outputs)
S1, S2, S3, S4,
S5, SC
Use the internal LVLC power supply of the drive.
Use class 2 for external power supply.
Main speed frequency reference input
(analog input)
+V, A1, AC
Use the internal LVLC power supply of the drive.
Use class 2 for external power supply.
Model
CIMR-J
Non-Time Delay
Class-T Fuse Type
(Manufacturer: Ferraz)
Fuse Ampere
Rating (A)
Fuse Type
(Manufacturer:
Bussmann)
500 Vac, 200 kAIR
Fuse Ampere
Rating (A)