◆ J1000 Finless Drive Watt Loss Thermal Characteristics
■ Normal Duty
Table 6 Drive Watt Loss (Normal Duty Rating)
Note: Carrier frequency is set to 2 kHz.
200 V Single-Phase Class
Model
CIMR-JBA
0001 0002 0003 0006 0010 – – – –
Rated Output Current (A) 1.2 1.9 3.3 6.0 9.6 – – – –
Generated Heat
Loss
Heatsink Plate
(W)
5.0 7.6 14.6 30.1 51.7 – – – –
Internal (W) 8.0 9.7 14.4 19.4 29.8 – – – –
Total (W) 13.5 17.3 29.0 49.5 81.5 – – – –
200 V Three-Phase Class
Model
CIMR-J2A
0001 0002 0004 0006 0008 0010 0012 0018 0020
Rated Output Current (A) 1.2 1.9 3.5 6.0 8.0 9.6 12.0 17.5 19.6
Generated Heat
Loss
Heatsink Plate
(W)
5.0 7.6 15.8 27.5 44.6 51.7 61.3 89.8 98.7
Internal (W) 8.0 9.5 13.6 17.2 24.0 25.8 30.4 44.1 46.3
Total (W) 13.0 17.1 29.4 44.7 68.6 77.5 91.7 133.9 145.0
400 V Three-Phase Class
Model
CIMR-J4A
0001 0002 0004 0005 0007 0009 0011 – –
Rated Output Current (A) 1.2 2.1 4.1 5.4 6.9 8.8 11.1 – –
Generated Heat
Loss
Heatsink Plate
(W)
10.0 18.5 30.5 44.5 58.5 63.7 81.7 – –
Internal (W) 9.6 13.9 16.8 21.8 28.5 31.4 46.0 – –
Total (W) 19.6 32.4 47.3 66.3 87.0 95.1 127.7 – –