3 Conditions of Acceptability
14 YAS KAWA ELECT RI C TOBP C710606 40A YASKAWA AC Drive - J1000 Finless Installation Manual
■ Heavy Duty
Table 7 Drive Watt Loss (Heavy Duty Rating)
200 V Single-PhaseClass
Model
CIMR-JBA
<1> Carrier frequency is set to 10 kHZ.
<2> Carrier frequency is set to 8 kHZ.
0001
<1>
0002
<1>
0003
<1>
0006
<1>
0010
<2>
––––
Rated Output Current (A) 0.8 1.6 3.0 5.0 8.0 ––––
Generated Heat
Loss
Heatsink Plate (W) 4.3 7.9 16.1 33.7 54.8 ––––
Internal (W) 7.4 8.9 11.5 16.8 25.9 ––––
Total (W) 11.7 16.8 27.6 50.5 80.7 ––––
200 V Three-Phase Class
Model
CIMR-J2A
0001
<1>
0002
<1>
0004
<1>
0006
<1>
0008
<1>
0010
<2>
0012
<2>
0018
<2>
0020
<2>
Rated Output Current (A) 0.8 1.6 3.0 5.0 6.9 8.0 11.0 14.0 17.5
Generated Heat
Loss
Heatsink Plate (W) 4.3 7.9 16.1 27.4 48.7 54.8 70.7 92.6 110.5
Internal (W) 7.3 8.8 11.5 15.9 22.2 23.8 30.0 38.8 43.3
Total (W) 11.6 16.7 27.6 43.3 70.9 78.6 100.7 131.4 153.8
400 V Three-Phase Class
Model
CIMR-J4A
0001
<2>
0002
<2>
0004
<2>
0005
<2>
0007
<2>
0009
<2>
0011
<2>
––
Rated Output Current (A) 1.2 1.8 3.4 4.8 5.5 7.2 9.2 – –
Generated Heat
Loss
Heatsink Plate (W) 19.2 28.9 42.3 70.7 81.0 84.6 107.2 – –
Internal (W) 11.4 14.9 17.9 26.2 30.7 32.9 41.5 – –
Total (W) 30.6 43.8 60.2 96.9 111.7 117.5 148.7 – –