8 YASKAWA ELECTRIC TOBP C710606 40A YASKAWA AC Drive - J1000 Finless Installation Manual
3 Conditions of Acceptability
3 Conditions of Acceptability
Adhere to the installation conditions specified in this manual to take full advantage of the
finless design of this drive.
Ambient Temperature
The drive ambient temperature shall not exceed 50 ºC (122 ºF) for the drives installed
location.
Heatsink Plate Temperature
The aluminum panel on the back of the drive is referred to as the “heatsink plate.” The
heatsink plate temperature should never exceed 90 °C
Table 6 and Table 7 lists the thermal characteristics of the drive.
Use parameter U4-08 to check the temperature of the heatsink plate as described below.
NOTICE: The drive may be damaged if the temperature of the heatsink plate exceeds specified tolerance
level (90 °C). Excessive heat can also shorten the performance life of various drive components.
Checking and Monitoring Heatsink Plate Temperature
Checking Heatsink Plate Temperature Using the LED Operator
Scroll to parameter U4-08 (heatsink plate temperature).
When the temperature of the heatsink plate is 89 ºC, U4-08 will display:
Checking Heatsink Plate Temperature Using an Analog Output
Example: When using Multi-Function Analog Output Terminal AM, set the parameters
shown in Table 1.
Table 1 Using Analog Output 1
No. Name Description
H4-01 Analog Output Terminal AM Function Selection
00408
(heatsink plate temperature)
H4-02 Analog Output Terminal AM Gain 100.0%
H4-03 Analog Output Terminal AM Bias 0.0%