2 Installation
E-14
2.2
Control Panel Cooling Method
The components that are used in the MP3300* require the ambient oper-
ating temperature to be between 0 and 60°C. Use one of the methods
described below to ensure adequate cooling in the control panel.
* The MP3300 includes CPU Module and base Unit.
Control Panels with Natural Cooling
Do not mount the MP3300 at the top of the control panel, where the hot
air that is generated inside the panel collects.
Leave sufficient space above and below the MP3300, and maintain ade-
quate distances from other devices, cable ducts, and other objects to
ensure suitable air circulation.
Do not mount the MP3300 in any direction other than the specified direc-
tion.
Do not mount the MP3300 on top of any device that generates a signifi-
cant amount of heat.
Do not subject the MP3300 to direct sunlight.
If the ambient temperature exceeds 55°C, use forced-air
cooling.