8.1 Alarm Displays
8.1.2 Troubleshooting Alarms
8-26
A.C20:
Phase Detection
Error
The linear encoder
signal level is too low.
Check the voltage of
the linear encoder sig-
nal.
Fine-tune the mounting of
the scale head. Or,
replace the linear
encoder.
The count-up direc-
tion of the linear
encoder does not
match the forward
direction of the Mov-
ing Coil in the motor.
Check the setting of
Pn080 = n.X
(Motor Phase Selec-
tion). Check the installa-
tion orientation for the
linear encoder and
Moving Coil.
Change the setting of
Pn080 = n.X.
Correctly reinstall the lin-
ear encoder or Moving
Coil.
*1
The polarity sensor
signal is being
affected by noise.
Correct the FG wiring.
Implement countermea-
sures against noise for the
polarity sensor wiring.
The setting of Pn282
(Linear Encoder Pitch)
is not correct.
Check the setting of
Pn282 (Linear Encoder
Pitch).
Check the specifications
of the linear encoder and
set a correct value.
*1
A.C21:
Polarity Sensor
Error
The polarity sensor is
protruding from the
Magnetic Way of the
motor.
Check the polarity sen-
sor.
Correctly reinstall the
Moving Coil or Magnetic
Way of the motor.
The polarity sensor is
not wired correctly.
Check the wiring of the
polarity sensor.
Correct the wiring of the
polarity sensor.
The polarity sensor
failed.
Replace the polarity sen-
sor.
A.C22:
Phase
Information
Disagreement
The SERVOPACK
phase information is
different from the lin-
ear encoder phase
information.
Perform polarity detec-
tion.
*1
Continued on next page.
Continued from previous page.
Alarm Number:
Alarm Name
Possible Cause Confirmation Correction Reference