IM 01E21A21-02EN
<2. Safety Instrumented Systems Installation>
7
Example of generating an alarm current output;
(In case of “66:Dens cfg ERR” for BRAIN (“Density conguration error” for HART));
(1) Set parameters through BRAIN or HART communication protocol in order to generate an alarm at “Analog
Output 1” by making a condition of scale out at its high limit side of current value.
BRAIN: G04: AO1 ALM OUT
HART Menu Path:
Device root menuDetailed setupAnalog output/inputAnalog output 1AO1 alarm out
Select “> 21.6 mA” when generating an alarm for its high limit side.
(a) BRAIN: H30: DENSITY SEL
HART Menu Path:
Device root menuDetailed setupProcess variablesDensityDensity value select
Select “Fixed value” above menu.
(b) BRAIN: H32: FIXED DENS
HART Menu Path:
Device root menuDetailed setupProcess variablesDensityDensity xed value
Set the parameter as “0.0” above menu.
(c) BRAIN: C30: PV FLOW SEL
HART Menu Path:
Device root menuDetailed setupProcess variablesPV ow select
Select “Mass” above menu.
An alarm, which was set at “Analog Output 1”, is generated and appeared at the result of above work.
(2) Set parameters through BRAIN or HART communication protocol in order to generate an alarm at “Analog
Output 1” by making a condition of scale out at its low limit side of current value.
BRAIN: G04: AO1 ALM OUT
HART Menu Path:
Device root menuDetailed setupAnalog output/inputAnalog output 1AO1 alarm out
Select “< 2.4 mA” when generating an alarm for its low limit side.
(a) BRAIN: H30: DENSITY SEL
HART Menu Path:
Device root menuDetailed setupProcess variablesDensityDensity value select
Select “Fixed value” above menu.
(b) BRAIN: H32: FIXED DENS
HART Menu Path:
Device root menuDetailed setupProcess variablesDensityDensity xed value
Set the parameter as “0.0” above menu.
(c) BRAIN: C30: PV FLOW SEL
HART Menu Path:
Device root menuDetailed setupProcess variablesPV ow select
Select “Mass” above menu.
An alarm, which was set at “Analog Output 1”, is generated and appeared at the result of above work.

Other manuals for YOKOGAWA AXW4A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA AXW4A and is the answer not in the manual?

YOKOGAWA AXW4A Specifications

General IconGeneral
BrandYOKOGAWA
ModelAXW4A
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals