EasyManuals Logo

YOKOGAWA EJX110A User Manual

YOKOGAWA EJX110A
57 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
<2. Handling Cautions>
27
IM01C25A01-01E
e. IECEx Flameproof Type
CautionforIECExameprooftype.
Note1. EJX/EJA-ESeriespressuretransmitterswith
optionalcode/SF2or/SU21areapplicablefor
useinhazardouslocations:
• No.IECExCSA07.0008
• ApplicableStandard:IEC60079-0:2011,
IEC60079-1:2007-4
• FlameproofforZone1,ExdIICT6...T4Gb
• Enclosure:IP66/IP67
• MaximumProcessTemperature:12C(T4),
10C(T5),85°C(T6)
• AmbientTemperature:–50to75°C(T4),
–50to80°C(T5),–50to75°C(T6)
• SupplyVoltage:42Vdcmax.
32Vdcmax.(FOUNDATIONFieldbusand
PROFIBUSPAtype)
9to28Vdc,27mW(LowPowertype)
9to30Vdc,250mW(RS485Modbus
CommunicationType)
• OutputSignal:4to20mAdc
15 mA (FOUNDATIONFieldbusandPROFIBUSPA
type)
1to5V(LowPowertype)
RS485Modbus(RS485ModbusCommunication
Type)
Note2. Wiring
• Inhazardouslocations,thecableentrydevices
shallbeofacertiedameprooftype,suitablefor
theconditionsofuseandcorrectlyinstalled.
• Unusedaperturesshallbeclosedwithsuitable
ameproofcertiedblankingelements.
• WiringconnectionforoutputsignalcodeQ(Low
Powertype)shallfollowthediagrambelow.
F0221.ai
Three-Wire Connection
Pressure Transmitters
Power Supply
Voltmeter
SUPPLY
+
SUPPLY
A
+
+
Four-Wire Connection
Pressure Transmitters
Power Supply
Voltmeter
SUPPLY
+
SUPPLY
A
+
+
Note3. Operation
• WARNING:
AFTERDE-ENERGIZING,DELAY5MINUTES
BEFOREOPENING.
• WARNING:
WHENTHEAMBIENTTEMP.≥65°C,USEHEAT-
RESISTINGCABLEANDCABLEGLAND≥90°C.
• Takecarenottogeneratemechanicalsparking
whenaccessingtotheinstrumentandperipheral
devicesinahazardouslocation.
• Electrostaticchargemaycauseanexplosion
hazard.Avoidanyactionsthatcausethe
generationofelectrostaticcharge,suchasrubbing
withadryclothoncoatingfaceoftheproduct.
Note4. MaintenanceandRepair
• Theinstrumentmodicationorpartsreplacement
byotherthanauthorizedrepresentativeof
YokogawaElectricCorporationisprohibitedand
willvoidIECExCertication.
• ElectricalConnection
Amarkindicatingtheelectricalconnectiontypeis
stampedneartheelectricalconnectionport.These
marksareasfollowed.
F0222.ai
Location of the mark
Screw Size Marking
ISO M20 × 1.5 female
ANSI 1/2 NPT female
M
N or W
2.5 EMC Conformity Standards
EN61326-1ClassA,Table2(foruseinindustrial
locations)
EN61326-2-3
EN61326-2-5(forFieldbus)
CAUTION
TomeetEMCregulations,Yokogawarecommends
thatcustomersrunsignalwiringthroughmetal
conduitsoruseshieldedtwisted-paircablingwhen
installingEJX/EJA-ESeriestransmittersinaplant.