<2. Handling Cautions>
28
IM01C25A01-01E
2.6 Pressure Equipment
Directive (PED)
(1) General
• EJX/EJA-ESeriespressuretransmittersare
categorizedaspipingunderthepressureaccessories
sectionofdirective2014/68/EU,whichcorresponds
toArticle4,Paragraph3ofPED,denotedasSound
Engineering Practice (SEP).
• EJX110A-MS,EJX110A-HS,
EJX110A-VS,EJA110Ewith/HG,EJ130,
EJ440,EJ510-D,EJ530-D,
EJX610A-D,andEJX630A-Dcanbeusedabove
200barandthereforeconsideredasapartofa
pressureretainingvesselwherecategoryIII,Module
Happlies.Thesemodelswithoptioncode/PE3
conformtothatcategory.
(2) Technical Data
• Modelswithout/PE3
Article4,Paragraph3ofPED,denotedasSound
Engineering Practice (SEP).
• Modelswith/PE3
Module:H
TypeofEquipment:PressureAccessory-Vessel
Typeofuid:LiquidandGas
Groupofuid:1and2
Model
Capsule
code
PS*
1
(bar)
V(L)
PS.V
(bar.L)
Category*
2
EJA110E M,H,V
160 0.01 1.6
Article4,
Paragraph3
(SEP)
EJ110
F,L
EJX110A
M,H,V 250 0.01 2.5
EJA110E
withcode
/HG
EJ110
withcode/
PE3
M,H,V 250 0.01 2.5 III
EJ130
M,H 500 0.01 5.0
Article4,
Paragraph3
(SEP)
EJ130
withcode/
PE3
M,H 500 0.01 5.0 III
EJ310
L,M,A,B 160 0.01 1.6
Article4,
Paragraph3
(SEP)
EJ430
H,A,B 160 0.01 1.6
Article4,
Paragraph3
(SEP)
EJ440
C,D 500 0.1 5.0
Article4,
Paragraph3
(SEP)
EJ440
withcode/
PE3
C,D 500 0.1 5.0 III
Model
Capsule
code
PS*
1
(bar)
V(L)
PS.V
(bar.L)
Category*
2
EJ510
EJX610A
A,B,C 100 0.1 10
Article4,
Paragraph3
(SEP)
D 700 0.1 70
EJ510,
EJX610A
withcode/
PE3
D 700 0.1 70 III
EJ530,
EJX630A
A,B,C 100 0.1 10
Article4,
Paragraph3
(SEP)
D 700 0.1 70
EJ530,
EJX630A
withcode/
PE3
D 700 0.1 70 III
EJX910A
L 160 0.01 1.6
Article4,
Paragraph3
(SEP)
M,H 250 0.01 2.5
EJX910A
withcode/
PE3
M,H 250 0.01 2.5 III
EJX930A M,H 500 0.01 5.0
Article4,
Paragraph3
(SEP)
EJX930A
withcode/
PE3
M,H 500 0.01 5.0 III
*1: PSismaximumpressureforvesselitselfbasedon
PressureEquipmentDirective2014/68/EU.Referto
GeneralSpecicationformaximumworkingpressureofa
transmitter.
*2: ReferredtoTable1coveredbyANNEXIIofECDirective
onPressureEquipmentDirective2014/68/EU.
(3) Operation
CAUTION
• Thetemperatureandpressureofuidshould
bemaintainedatlevelsthatareconsistentwith
normal operating conditions.
• Theambienttemperatureshouldbemaintained
atalevelthatisconsistentwithnormaloperating
conditions.
• Pleasetakecaretopreventwaterhammerandthe
likefrominducingexcessivepressuresinpipes
andvalves.Ifphenomenaarelikely,installasafety
valveortakesomeotherappropriatemeasureto
preventpressurefromexceedingPS.
• Takeappropriatemeasuresatthedeviceor
systemleveltoprotecttransmittersiftheyaretobe
operatednearanexternalheatsource.