<5. Wiring>
40
IM01C25A01-01E
5. Wiring
NOTE
For FOUNDATIONFieldbus,PROFIBUSPA,andMod
buscommunicationtypes,pleaserefertoeach
communication manual.
5.1 Wiring Precautions
IMPORTANT
• Laywiringasfaraspossiblefromelectricalnoise
sourcessuchaslargecapacitytransformers,
motors,andpowersupplies.
• Removeelectricalconnectiondustcapbefore
wiring.
• Allthreadedpartsmustbetreatedwith
waterproongsealant.(Anon-hardeningsilicone
group sealant is recommended.)
• Topreventnoisepickup,donotpasssignaland
powercablesthroughthesameducts.
• Explosion-protectedinstrumentsmustbewired
inaccordancewithspecicrequirements(and,
incertaincountries,legalregulations)inorder
topreservetheeffectivenessoftheirexplosion-
protected features.
• TheterminalboxcoverislockedbyanAllenhead
bolt(ashroudingbolt)onATEXameprooftype
transmitters.Whentheshroudingboltisdriven
clockwiseusinganAllenwrench,itgosein.The
coverlockcanthenbereleasedandthecovercan
beopenedbyhand.
Whenacoveriscloseditshouldbelockedbya
shroudingboltwithoutfail.Tightentheshrouding
bolttoatorqueof0.7N·m.
Shrouding Bolt
Shrouding Bolt
F0501.ai
Figure 5.1 Shrouding Bolt
• Plugandsealanunusedconduitconnection.
5.2 Connections of External
Wiring to Terminal Box
F0527.ai
RTD cable connection*
● Terminal Configuration
1
Terminal
2
Terminal
3
Terminal
[A]
[B]*
*For EJX9A only.
4
Terminal
Power supply and output terminals
External indicator (ammeter) terminals
*1*2
or
Status contact output terminals
*2
(when /AL is specified)
● Terminal Wiring for 4 to 20 mA output
SUPPLY
CHECK
or
ALARM
+
+
+
Ground terminal
1
2
2
2
3
3
F0528.ai
SUPPLY
VOUT
+
+
● Terminal Wiring for 1 to 5 V output
Ground terminal
Power supply terminals
1 to 5 V DC with HART communication
terminals
1
2
2
3
*1: When using an external indicator or check meter, the
internal resistance must be 10 Ω or less. A check meter
or indicator cannot be connected when /AL option is
specified.
*2: Not available for F
OUNDATION Fieldbus and PROFIBUS
PA communication types.
SUPPLY
CHECK
PULSE
+
*1: When using an external indicator or check meter, the
internal resistance must be 10Ω or less.
*2: Not available for FOUNDATION Fieldbus communication
type.
+
+
● Terminal Wiring for 4 to 20 mA output
[EJX9A]
Ground terminal
Power supply and output terminals
External indicator (ammeter) terminals
*1*2
Pulse or status contact output terminals
*2
1
2
2
3
2
4
Figure 5.2 Terminal