10
P5415484
Table A: Optional Setting Items for Function Selection
No. Items Optional Function
Individual
Setting
Setting
Condition
Contents Setting
1b1
Cancellation of Heating
Temperature Compensation
due to Uneven Heat Load
00
01
02
03
04
Standard (Set Temp. +7
o
F (+4
o
C)) (*1)
Removal (Set Temp.)
Set Temp. +3
o
F (+2
o
C) (*2)
Set Temp. +5
o
F (+3
o
C)
Set Temp. +2
o
F (+1
o
C)
2b2
Circulator Function during
Heating Thermo-OFF
00
01
Not Available
Available
3 b3 Not Prepared - - Not Used (Use as 00 setting conditions)
4 b4 Change of Filter Cleaning Time
00
01
02
03
04
Standard 1,200 hrs (Factory-Setting)
100 hrs
1,200 hrs
2,500 hrs
No Indication
5 b5 Fixing (Locking) Operation Mode
×
00
01
Standard
Fixed (Locked)
6b6
Fixing (Locking) Setting Temperature
(*2)
×
00
01
Standard
Fixed (Locked)
7b7
Fixing (Locking) Operation as
Exclusive Cooling Unit
×
00
01
Standard
Fixed (Locked)
8 b8 Automatic COOL/HEAT Operation
×
00
01
Not Available
Available
9 b9 Fixing (Locking) Fan Speed
×
00
01
Standard
Fixed (Locked)
10 bA Not Prepared - - Not Used
11 bb
Cooling Temperature Compensation
due to Uneven Heat Load
×
00
01
02
Standard (No Compensation)
Set Temp. –2
o
F (–1
o
C)
Set Temp. –3
o
F (–2
o
C)
12 bC Not Prepared - - Not Used (Use as 00 setting conditions)
13 bd Not Prepared - - Not Used (Use as 00 setting conditions)
14 bE Not Prepared - - Not Used (Use as 00 setting conditions)
15 C1 Not Prepared - - Not Used (Use as 00 setting conditions)
16 C2 Not Prepared - - Not Used
17 C3 Not Prepared - - Not Used
18 C4 Not Prepared - - Not Used
19 C5
Hi Speed
(Except for Hi Speed during Heating
Thermo-OFF)
00
01
02
Not Available
Hi Speed 1 (*3)
Hi Speed 2
20 C6
Hi Speed during Heating Thermo-
OFF
00
01
Not Available
Available
21 C7
Canceling of Enforced 3 Minutes
Minimum Operation Time of
Compressor
00
01
Standard
Cancelation
22 C8 Thermistor of Wired Controller
00
01
02
00
01
02
< If Wired Controller Thermistor is Selected ˃
Not Available
Control by Thermistor of Wired Controller
Control by Average Value of Indoor Suction
Thermistor and Thermistor of Wired Controller
< If Remote Sensor is Selected ˃
Control by Average Value of Indoor Suction
Thermistor and Remote Sensor
Control by Remote Sensor
Same as "00"
23 C9 Not Prepared - - Not Used
24 CA Not Prepared - - Not Used
25 Cb Selection of Forced Stoppage Logic
00
01
Forced Stoppage Input: A Contact
Forced Stoppage Input: B Contact
26 CC Not Prepared - - Not Used (Use as 00 setting conditions)
27 Cd Not Prepared - - Not Used (Use as 00 setting conditions)
28 CE Not Prepared - - Not Used (Use as 00 setting conditions)