No. Items Optional Function
Individual
Setting
Setting
Condition
Contents Setting
118 q2 Auxiliary Heater ON Compensation
×
-3(-1.5)
-4(-2.5)
-5(-3.0)
-6(-3.5)
-7(-4.0)
-8(-4.5)
-9(-5.0)
-1(-0.5)
-2(-1.0)
-3
o
F (-1.5
o
C)
-4
o
F (-2.5
o
C)
-5
o
F (-3.0
o
C)
-6
o
F (-3.5
o
C)
-7
o
F (-4.0
o
C)
-8
o
F (-4.5
o
C)
-9
o
F (-5.0
o
C)
-1
o
F (-0.5
o
C)
-2
o
F (-1.0
o
C)
119 q3 Auxiliary Heater OFF Compensation
×
0(0.0)
1(0.5)
0
o
F (0.0
o
C)
1
o
F (0.5
o
C)
120 q4
Ambient Temperature Restriction
Setpoint
×
-4
(-20.0)
2
(-17.0)
8
(-13.0)
14
(-10.0)
20
(- 7.0)
26
(- 3.0)
32
( 0.0)
-13
(-25.0)
-8
(-22.0)
-4
o
F (-20.0
o
C)
2
o
F (-17.0
o
C)
8
o
F (-13.0
o
C)
14
o
F (-10.0
o
C)
20
o
F (- 7.0
o
C)
26
o
F (- 3.0
o
C)
32
o
F ( 0.0
o
C)
-13
o
F (-25.0
o
C)
-8
o
F (-22.0
o
C)
121 q5
Ambient Temperature Restriction
Setpoint Compensation
×
4(2.5)
5(3.0)
6(3.5)
1(0.5)
2(1.0)
3(1.5)
4
o
F (2.5
o
C)
5
o
F (3.0
o
C)
6
o
F (3.5
o
C)
1
o
F (0.5
o
C)
2
o
F (1.0
o
C)
3
o
F (1.5
o
C)
122 q6 Heater Select
×
00
01
Duct Heater
Baseboard Heater
123 q7 Emergency Heat Control
×
00
01
Available
Not Available
124 q8 Not Prepared - - Not Used (Use as 00 setting conditions)
125 q9 Not Prepared - - Not Used (Use as 00 setting conditions)
126 qA Not Prepared - - Not Used (Use as 00 setting conditions)
127 qb Mode with Setback
×
00
01
02
03
Not Available
COOL only
HEAT only
COOL HEAT
128 qC
Temp. Difference during Setback
Operation
×
00
01
02
03
04
3°F (2.0°C)
5°F (3.0°C)
7°F (4.0°C)
9°F (5.0°C)
2°F (1.0°C)
129 qd Minimum Setback (Stop) Time
×
00
01
02
03
04
05
06
07
08
09
10
11
10 min.
20 min.
30 min.
40 min.
50 min.
60 min.
70 min.
80 min.
90 min.
100 min.
110 min.
120 min.
130 qE Setback Mode
×
00
01
02
03
Always
Input
Scheduling
Manual
131 qF
Operation State after Terminating
Setback Operation
×
00
01
02
Stop
Run
State before Setback Operation
132 r1 Dual Setpoint
×
00
01
Not Available
Available