5120416-XIM-C-0216
18 Johnson Controls Unitary Products
Table 6: Electrical Data
DC Electrical Data -without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
(Amps)
Max Fuse/
Breaker
1
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
180
(15)
380-3-50 10.3 62 16 2.1 6.3 0
NONE - - - 44 50
E18 11.3 1 17.2 44 50
E36 22.6 2 34.3 50.8 60
E54 33.8 2 51.4 72.1 80
E72 45.1 2 68.5 93.5 100
415-3-50 10.3 62 16 2.1 6.7 0
NONE - - - 44.4 50
E18 13.5 1 18.8 44.4 50
E36 26.9 2 37.4 55.2 60
E54 40.4 2 56.2 78.6 80
E72 53.8 2 74.8 83.2 90
240
(20)
380-3-50 20.7 130 29 2.1 8.2 0
NONE - - - 59 70
E18 11.3 1 17.2 59 70
E36 22.6 2 34.3 59 70
E54 33.8 2 51.4 74.4 80
E72 45.1 2 68.5 95.9 100
415-3-50 20.7 130 29 2.1 9.1 0
NONE - - - 59.9 80
E18 13.5 1 18.8 59.9 80
E36 26.9 2 37.4 59.9 80
E54 40.4 2 56.2 81.6 90
E72 53.8 2 74.8 86.2 100
300
(25)
380-3-50 22.9 145 32 2.1 15.2 0
NONE - - - 70.9 90
E18 11.3 1 17.2 70.9 90
E36 22.6 2 34.3 70.9 90
E54 33.8 2 51.4 83.2 90
E72 45.1 2 68.5 104.7 110
415-3-50 22.9 145 32 2.1 14.6 0
NONE - - - 70.3 90
E18 13.5 1 18.8 70.3 90
E36 26.9 2 37.4 70.3 90
E54 40.4 2 56.2 88.5 90
E72 53.8 2 74.8 93.1 100
1. HACR Type per NEC.