DM300 UNIT - DOWNFLOW DUCT CONNECTIONS (CFM)
BLOWER
SPE
ED (rpm)
PULLEY
TURNS OPEN
7500 CFM 8750 CFM 10000 CFM
ESP (iwg) OUTPUT (bhp) INPUT (kW) ESP (iwg) OUTPUT (bhp)
INPUT
(kW)
ESP (iwg) OUTPUT (bhp)
INPUT
(kW)
945 6.0 1.2 5.6 4.6 0.8 7.0 5.7 0.3 8.4 6.9
975 5.0 1.4 5.9 4.9 1.0 7.3 6.0 0.5 8.8 7.2
1005 4.0 1.6 6.2 5.1 1.2 7.7 6.3 0.7 9.2 7.6
1040 3.0 1.8 6.6 5.4 1.4 8.1 6.7 0.9 9.7 8.0
1070 2.0 2.0 6.9 5.7 1.6 8.5 7.0 1.1 10.2 8.3
1100 1.0 2.1 7.3 6.0 1.8 8.9 7.3 1.3 10.6 8.7
1130 0.0 2.3 7.6 6.2 2.0 9.3 7.6 1.5 11.0 9.0
DM300 UNIT - DOWNFLOW DUCT CONNECTIONS (m
3
/s)
BLOWER
SPE
ED (rpm)
PULLEY
TURNS OPEN
3.53 m
3
/Sec. 4.13 m
3
/Sec. 4.72 m
3
/Sec.
ESP (Pa) OUTPUT (bhp) INPUT (kW) ESP (Pa) OUTPUT (bhp)
INPUT
(kW)
ESP (Pa) OUTPUT(bhp)
INPUT
(kW)
945 6.0 303 5.6 4.6 198 7.0 5.7 71 8.4 6.9
975 5.0 347 5.9 4.9 244
7.3 6.0 120 8.8 7.2
1005 4.0 391 6.2 5.1 291 7.7 6.3 169 9.2 7.6
1040 3.0 443 6.6 5.4 347 8.1 6.7 228 9.7 8.0
1070 2.0 489 6.9 5.7 396 8.5 7.0 280 10.2 8.3
1100 1.0 536 7.3 6.0 445 8.9 7.3 332 10.6 8.7
1130 0.0 583 7.6 6.2 495 9.3 7.6 385 11.0 9.0
DM300 UNIT - DOWNFLOW DUCT CONNECTIONS - GAS HEAT MODELS (CFM)
BLOWER
SPE
ED (rpm)
PULLEY
TURNS OPEN
7500 CFM 8750 CFM 10000 CFM
ESP (iwg) OUTPUT (bhp) INPUT (kW) ESP (iwg) OUTPUT (bhp)
INPUT
(kW)
ESP (iwg) OUTPUT (bhp)
INPUT
(kW)
945 6.0 1.0 5.6 4.6 0.3 7.0 5.7 - - -
975 5.0 1.2 5.9 4.9 0.5 7.3 6.0 - - -
1005 4.0 1.4 6.2 5.1 0.7 7.7 6.3 - - -
1040 3.0 1.6 6.6 5.4 0.9 8.1 6.7 0.2 9.7 8.0
1070 2.0 1.8 6.9 5.7 1.1 8.5 7.0 0.4 10.2 8.3
1100 1.0 2.0 7.3
6.0 1.3 8.9 7.3 0.6 10.6 8.7
1130 0.0 2.2 7.6 6.2 1.5 9.3 7.6 0.8 11.0 9.0
DM300 UNIT - DOWNFLOW DUCT CONNECTIONS - GAS HEAT MODELS (m
3
/s)
BLOWER
SPE
ED (rpm)
PULLEY
TURNS OPEN
3.53 m
3
/sec. 4.13 m
3
/sec. 4.72 m
3
/sec.
ESP (Pa) OUTPUT (bhp) INPUT (kW) ESP (Pa) OUTPUT (bhp)
INPUT
(kW)
ESP (Pa) OUTPUT (bhp)
INPUT
(kW)
945 6.0 258 5.6 4.6 87 7.0 5.7 - - -
975 5.0 301 5.9 4.9 133 7.3 6.0 - - -
1005 4.0 345 6.2 5.1 180 7.7 6.3 - - -
1040 3.0 398 6.6 5.4 236 8.1 6.7 43 9.7 8.0
1070 2.0 444 6.9 5.7 285 8.5 7.0 94 10.2 8.3
1100 1.0 490 7.3 6.0 334 8.9 7.3 146 10.6 8.7
1130 0.0 537 7.6 6.2 384 9.3 7.6 199 11.0 9.0
NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2.Refer to the additional Static Resistances table.
ESP = External Static Pressure available fo
r the supply and return air duct system. All internal unit resistances have been deducted from the total static
pressure of the blower.
* Do
NOT close the pulley below 1 turn open.
** Factory setting.
Supply Air Blower Performance (25 Ton) - Cooling Applications 300 Mbh - Bottom Duct Connections