INSTALLATION
MANUAL
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU
START TO INSTALL YOUR UNIT.
SAVE THIS MANUAL
SINGLE PIECE AIR HANDLERS
HEAT PUMP MODELS
F2RP / F2FP018 THRU 060
F3RP / F3FP018 THRU 060
COOLING MODELS
F2RC / F2FC 024 THRU 036
035-14520-001 Rev. B (0803)
TABLE OF CONTENTS
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . 2
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
REFERENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
HORIZONTAL DRAIN PAN INSTALLATION /
CONVERSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DUCT CONNECTORS . . . . . . . . . . . . . . . . . . . . . . . . . . 5
AIR FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
SUSPENSION KITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
COIL METERING DEVICES . . . . . . . . . . . . . . . . . . . . . . 6
REFRIGERANT LINE CONNECTION . . . . . . . . . . . . . . . 7
ELECTRIC HEATERS & OPERATING CONTROLS . . . 8
LOW VOLTAGE CONTROL CONNECTION . . . . . . . . . . 8
LINE POWER CONNECTIONS . . . . . . . . . . . . . . . . . . . . 8
BLOWER SPEED CONNECTIONS . . . . . . . . . . . . . . . . 8
DRAIN CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . 19
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
COIL CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
LUBRICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
CONDENSATE DRAINS . . . . . . . . . . . . . . . . . . . . . . . . 19
TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . . . . 19

Questions and Answers

  • R
    Robert DiazAug 8, 2025
    Why does my York Air Handler blower run all the time?
    • L
      luiswatsonAug 9, 2025
      If the blower in your York Air Handler is running continuously, here's what might be happening and how to address it: * **Thermostat Setting:** Ensure that the thermostat fan switch is set to the “AUTO” position, not “ON”. * **Blower Delay:** The blower might be in its normal OFF delay, which lasts approximately 1 minute. Wait and see if it stops. * **Connectors and Limits:** Check the installation of the 6-pin connector. Also, inspect the limit switch connection. * **Variable Speed Tab:** Look for a broken variable speed break-out tab.
  • S
    Steve EstradaAug 14, 2025
    What to do if my York Air Handler has no heat or limited heating?
    • C
      Christopher Murray DDSAug 14, 2025
      If your York Air Handler isn't providing enough heat, or no heat at all, here are a few things to check: 1. **Airflow:** Make sure that all registers are open and that there are no obstructions restricting airflow to either the supply or return registers. 2. **Filter:** Inspect the filter and replace it if it's dirty. 3. **Blower Motor:** Check to ensure the blower motor is functioning correctly. 4. **Safety Limit:** If the safety limit has opened 4 times, the control will prevent the heating element from operating for 1 hour. Allow the control to reset.
  • F
    Frank DavisAug 21, 2025
    How to troubleshoot no 2nd stage heat in York F2FP048?
    • F
      felicia24Aug 21, 2025
      If your York Air Handler is not providing 2nd stage heat, here’s what you should check: * **Connectors and Relays:** Inspect the 6-pin connector and the connections to the panel mount relays. * **Terminal Strip Connections:** Verify that both W1 and W2 are securely connected at the terminal strip.
  • L
    lambertmeghanAug 27, 2025
    What to do if my York Air Handler has no 24V?
    • L
      lmolinaAug 27, 2025
      If your York Air Handler has no 24V, here are a few things to check: * **4-Pin Connector:** Ensure the 4-pin connector is securely in place. * **Wiring:** Inspect and secure any loose wire connections from the control to the transformer (both 24V and 230V). * **Fuse:** Replace any blown fuse located on the control board.
  • K
    Kevin PerrySep 2, 2025
    Why does my York F2FP048 Air Handlers keep blowing fuses?
    • D
      Dustin Burke MDSep 2, 2025
      To address a blown fuse in your York Air Handler, check for low voltage shorts to C or ground from R, Y, G, W, or O.

Summary

GENERAL INFORMATION

LOCATION

CAUTION: ELECTRIC HEAT CLEARANCE

Minimum 1-inch clearance for electric heat on all sides of supply air duct/plenum up to 3 feet.

HORIZONTAL DRAIN PAN INSTALLATION; CONVERSION

CAUTION: KNOCK OUT CUTOUT

Do not knock out horizontal drain cutout; use a utility knife.

CAUTION: HORIZONTAL APPLICATION

Move coil support bracket and rotate baffle for left-hand horizontal application.

AIR FILTERS

COIL METERING DEVICES

Explains orifice vs. TXV and their installation notes.

Orifice Metering Device

REFRIGERANT LINE CONNECTION

Connect refrigerant lines to the coil.

ELECTRIC HEATERS & OPERATING CONTROLS

PHYSICAL AND ELECTRICAL DATA

ELECTRICAL DATA - 1 Ø - 208;230-1-60

ELECTRICAL DATA - SINGLE SOURCE SUPPLY

ELECTRICAL DATA - MULTI-SOURCE SUPPLY

ELECTRICAL DATA - 1 Ø - 220;240-1-50

AIR FLOW DATA - HEAT PUMP MODELS

AIR FLOW DATA - 50 HZ MODELS

Cooling Wiring Diagrams

DRAIN CONNECTIONS

CAUTION: THREADED DRAIN CONNECTION

Threaded drain connection should be hand-tightened.

CAUTION: HORIZONTAL DRAIN CUTOUT

Remove horizontal drain cutout with a utility knife.

TROUBLESHOOTING GUIDE

Lists common problems and their possible causes.

York F2FP048 Specifications

General IconGeneral
Model NumberF2FP048
CategoryAir Handlers
Cooling Capacity4 tons
Airflow1600 CFM
Voltage208/230V
Phase1
Motor TypePSC
Cabinet ConstructionGalvanized steel