036-21096-001-C-0206
4 Unitary Products Group
SUPPLY AIR BLOWER PERFORMANCE*
RPM
CFM
6400 7200 8000 8800 9600
ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW ESP BHP KW
600 0.15 1.49 1.42 ------------
650 0.31 1.71 1.63 0.14 2.00 1.90 ---------
700 0.49 1.95 1.86 0.32 2.27 2.16 0.12 2.63 2.50 ------
750 0.67 2.21 2.10 0.51 2.56 2.44 0.32 2.92 2.78 0.10 3.35 3.19 - - -
800 0.85 2.50 2.38 0.70 2.85 2.71 0.52 3.25 3.09 0.31 3.70 3.52 0.07 4.20 4.00
850 1.05 2.80 2.66 0.91 3.19 3.04 0.74 3.61 3.44 0.53 4.07 3.87 0.29 4.62 4.40
900 1.25 3.11 2.96 1.12 3.55 3.38 0.96 3.99 3.80 0.76 4.51 4.29 0.53 5.07 4.82
950 1.46 3.46 3.29 1.34 3.92 3.73 1.18 4.43 4.22 1.00 4.97 4.73 0.78 5.53 5.26
1000 1.67 3.82 3.64 1.56 4.33 4.12 1.42 4.88 4.64 1.24 5.44 5.18 - - -
L EU 240 AIR FLOW PERFORMANCE
850R P M
800R P M
700R P M
750R P M
650R P M
600RPM
900R P M
950R P M
1000R P M
3 H P
2 H P
5 H P
4 H P
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
6400 7200 8000 8800 9600
Cubic Feet Per Minute (CFM)
Total External Static Pressure
WC"
*When determining required brake horsepower, select nearest HP to the right of selected CFM.
Horsepower ratings on the Airflow Chart are approximate values. To assure correct BHP, please refer to Supply
Air Blower Performance Chart at the top of the page.
http://www.rezine.ne