036-21338-001-C-0703
4 Unitary Products Group
TABLE 4: ELECTRICAL DATA
MODEL
(HA)
VOLTAGE
CODE
COMPRESSOR CONDENSER FAN MOTOR
UNIT
AMPACITY
(AMPS)
MAX.
FUSE
SIZE
*
(AMPS)
MIN.
WIRE
SIZE
†
(AWG)
POWER
SUPPLY
RLA LRA
POWER
SUPPLY
HP QTY FLA
2 208/230-3-60 25.6 190 208/230-1-60 3/4 2 3.03 38.1 60 8
090 4 460-3-60 13.5 95 460-1-60 3/4 2 1.60 20.1 30 10
5 575-3-60 10.2 75 575-1-60 3/4 2 1.35 15.5 25 10
*. Dual element.
†. Based on three, 60°C insulated copper conductors in steel conduit.
TABLE 5: UNIT COOLING CAPACITIES AND POWER REQUIREMENTS
MODEL
HA
SUCTION PRESS. &
CORRESPONDING
TEMP. @ SATURATION
TEMPERATURE OF AIR ON CONDENSER COIL, °F
65 75 85 95 105 115
PSIG °F MBH KW* MBH
KW
*
MBH KW* MBH KW* MBH KW* MBH KW*
090
61.6 35 94 6.7 90 7.2 85 7.8 80 8.3 75 9.1 70 9.8
68.5 40 104 6.8 99 7.3 94 7.9 89 8.5 84 9.2 78 9.9
76.0 45 114 6.8 109 7.4 103 8 98 8.6 93 9.3 87 10
84.0 50 124 6.9 119 7.5 113 8.1 108 8.7 102 9.4 96 10.2
*. Includes compressor and condenser fan motor(s).