036-21323-002-C-0206
Unitary Products Group 7
TABLE 1: UNIT APPLICATION DATA
Application Limitations Minimum Maximum
Voltage Variation (208/230-3-60) - Volts 187 253
Voltage Variation (460-3-60) - Volts 414 506
Voltage Variation (575-3-60) - Volts 540 630
Ambient Air on Outdoor Coil (Cooling Cycle) - F 45 115
Ambient Air on Indoor Coil (Cooling Cycle) - F 68 86
TABLE 2: ARI RATINGS - COOLING AND SOUND
Model
Cooling Capacity
1
Cond. Unit
Sound
2
Rated Airflow Rated ESP
Outdoor
Unit
Indoor Unit MBH EER IPLV dB CFM IWG
HB180 KB180 180 9.7 10.4 89.0 6000 0.35
HB240 KB240 240 9.7 10.4 90.0 8000 0.40
1. Ratings are in accordance with ARI standard 340/360.
2. Ratings are in accordance with ARI standard 370.
TABLE 3: ELECTRICAL DATA COMPRESSORS
Model
Number
Compressors
Power
Supply
System 1 System 2
RLA LRA RLA LRA
HB180 208/230-3-60 25.6 190.0 25.6 190.0
HB180 460-3-60 12.8 95.0 12.8 95.0
HB180 575-3-60 10.2 75 10.2 75
HB240 208/230-3-60 42.0 239.0 42.0 239.0
HB240 460-3-60 19.2 125.0 19.2 125.0
HB240 575-3-60 13.8 80 13.8 80
TABLE 4: ELECTRICAL DATA FAN MOTORS
Model
Number
Condenser Fans
Power
Supply
Qty.
FLA
ea.
HB180 208/230-3-60 2 3.7
HB180 460-3-60 2 1.85
HB180 575-3-60 2 1.7
HB240 208/230-3-60 2 5.8
HB240 460-3-60 2 2.9
HB240 575-3-60 2 2.2
TABLE 5: ELECTRICAL DATA, OUTDOOR MCA & MAX. FUSE SIZE
Model
Number
Power
Supply
Min. Circuit
Ampacity
Max.
Fuse
Size
1
HB180 208/230-3-60 65.1 90
HB180 460-3-60 32.5 45
HB180 575-3-60 26.4 35
HB240 208/230-3-60 106.1 125
HB240 460-3-60 49.0 60
HB240 575-3-60 35.5 45
1. Maximum fuse or maximum circuit breaker (HACR type per NEC).