Unitary Products Group 3
APPLICATION FLEXIBILITY
OUTDOOR UNITS
These outdoor units are lightweight and can be
installed on almost any roof.
Units can be lifted using nylon straps with hooks at the
holes provided in the base rails, or they may be lifted
with a forklift through the slotted openings in the base
rails.
A quality appearance and low sound levels make these
units suitable for most ground level locations.
Remember that during heat and defrost cycles, con-
densate will drip from the underside of the unit coils.
This condensate will freeze when the temperature of
the outdoor air is below 32°F. A gravel bed or some
other means of handling this condensate may have to
be provided.
VERTICAL / HORIZONTAL
The FA120 unit is shipped for vertical installation with a
vertical air discharge as shown in FIG. 2; but may be
converted to other arrangements per the following
instructions:
1. Remove the panels from the blower section.
2. Remove the four Phillips machine bolts that hold
the coil and blower sections together. A bolt is
located near each corner.
3. Move the blower section to the proper location.
4. Attach the blower section to the coil section with
the machine bolts removed in Step 2.
5. Before replacing the panel, see Duct Connection
and Drain Connection.
6. Replace the panels.
NOTE: See Figure -2 on next page for horizontal and
vertical application.
FIGURE 1 - TYPICAL RIGGING
5 Ft. Min.
FORKLIFT
OPENINGS