TABLE 4: HEATING CAPACITIES
HEATING APPLICATION DATA UNIT MODEL EF-10 60 HZ
CFM ID DB
OUTDOOR TEMPERATURE (F) (72% RH)
0 10203040506070
3000
60
MBH 13.058 35.855 58.653 81.451 104.249 127.047 149.844 172.642
3000 KW 2.805 4.421 6.038 7.654 9.270 10.887 12.503 14.120
3000
70
MBH 12.959 35.757 58.555 81.353 104.151 126.949 149.746 172.544
3000 KW 3.682 5.299 6.915 8.532 10.148 11.764 13.381 14.997
3000
80
MBH 12.312 35.110 57.908 80.706 103.503 126.301 149.099 171.897
3000 KW 4.697 6.313 7.930 9.546 11.162 12.779 14.395 16.012
4000
60
MBH 17.636 40.434 63.232 86.030 108.827 131.625 154.423 177.221
4000 KW 1.741 3.357 4.974 6.590 8.207 9.823 11.440 13.056
4000
70
MBH 17.554 40.352 63.150 85.948 108.745 131.543 154.341 177.139
4000 KW 2.623 4.240 5.856 7.473 9.089 10.705 12.322 13.938
4000
80
MBH 16.930 39.728 62.526 85.324 108.122 130.919 153.717 176.515
4000 KW 3.645 5.261 6.877 8.494 10.110 11.727 13.343 14.960
5000
60
MBH 18.690 41.488 64.285 87.083 109.881 132.679 155.477 178.274
5000 KW 1.586 3.202 4.819 6.435 8.052 9.668 11.284 12.901
5000
70
MBH 18.592 41.389 64.187 86.985 109.783 132.581 155.378 178.176
5000 KW 2.463 4.080 5.696 7.313 8.929 10.546 12.162 13.778
5000
80
MBH 17.944 40.742 63.540 86.338 109.136 131.933 154.731 177.529
5000 KW 3.478 5.094 6.711 8.327 9.944 11.560 13.176 14.793
THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.
FOR NET CAPACITY, ADD THE SUPPLY AIR BLOWER MOTOR HEAT (MBH = 3.415 X KW)
Cor rec tion Fac tor
% Nomi nal Sup ply Air CFM
8 0 90 100 110 12 0
MBH 0.96 0.98 1.00 1.02 1.04
KW 1.030 1.015 1.000 0.985 0.970
Out door Unit Size 7-1/2 Ton 10 Ton
Out door Fan Mo tor KW - 60 HZ 0.96 1.03
Out door Fan Mo tor KW - 50 HZ 0.80 0.85
1These ratings are based on an outdoor relative humidity of 72%. They include an allowance for defrost but not for the supply air blower motor heat. Refer to the BLOWER PERFORMANCE
table for the KW rating of the supply air blower motor at the design conditions. Convert this KW rating to MBH using the following equation and add this equivalent heat to the heating capacity.
Blower Motor Heat (MBH) = Blower Motor KW x (3.415 MBH/KW)
Use the following equation to determine the C.O.P. at any operating condition:
C.O.P. = Total MBH (Including Blower Motor Heat)/[Total KW (Including Blower Motor KW) x 3.415]
2Correct the MBH and KW ratings with the following factors for different supply air CFM's.
3These ratings include the compressor KW and the following KW for the outdoor fan motor(s).
NOTE: Apply these factors to the above ratings before correcting
for the supply air blower heat and power requirements.
Blower motor KW is not included. Refer to the SUPPLY AIR BLOWER PERFORMANCE table for the KW rating of the supply air blower motor at the design conditions and add this power
requirement to the KW rating.