Single Duct Variable Air Volume Terminal (Model TSS)
Bypass
Dimensions
Unit
Size CFM
CFM
Weight
W x H x L A I X Y
6 200 300 18 10” x 10" x 11" 6 1/2“ 5 7/8” 8 3/4” 8 3/4”
8 400 600 20 12” x 10” x 11" 6 1/2“ 7 7/8” 10 3/4” 8 3/4”
10 600 900 25 14” x 12.5" x 13” 6 1/2“ 9 7/8” 12 3/4” 11 1/4”
12 800 1200 30 16” x 15" x 13” 6 1/2“ 11 7/8” 14 3/4” 13 3/4”
14 1100 1800 38 20” x 17.5" x 17.5" 6 1/2“ 13 7/8” 18 3/4” 16 1/4”
16 1500 2200 42 24” x 17.5" x 17.5" 6 1/2“ 15 7/8” 22 3/4” 16 1/4”
22 3000 5400 72 34” x 17.5" x 11" 8” 32 1/4” x 15 7/8” 32 3/4” 16 1/4”
Note: All dimensions are in inches with a tolerance of +1/8”. Size 22 has a rectangular inlet collar. CFM based on
1000 FPM (Bypass 1500 FPM) for low to medium pressure applications.