8.12 Setback Operation
(1) Press and hold “Menu” and “Back/Help”on the wired controller simultaneously for at least three
seconds during the normal mode (unit stoppage).
The Test Run menu is displayed.
(2) Select “Input/Output” from the Test Run menu and press “OK”.
(3) Select either "Input 1" or "Input 2" and change the setting to "09".
(4) Build a circuit such as shown below.
(5) Temperature adjustment for the setback function can be selected on the wired controller.
Refer to Section 8.11, "Function Selection by Wired Controller" of the manual for details.
OK
Test Run Menu
Input/Output
Thermistor Selection
Function Selection
01
/
03
Test Run
Entr RtrnSel.
Back
Function 5
CN3
1
2
3
1
2
3
1
2
3
CN3
TB1
PSC-5RA
Card Key
oltage "a" Contact
When the card key is inserted (i.e.
someone is in the room), then the
contact turns ON.
Indoor Unit
Wired
OK
Input/Output:01-03
Input 1 00 CN3 1-2
Input 2 00 CN3 2-3
Output1 00 CN7 1-2
Output2 00 CN7 1-3
Output3 00 CN8 1-2
Item Setting Connector
Adj. Entr RtrnSel.
Back